STP-A Cabling

Cable and connector specifications extended to 300 MHz. (Prior specifications are no longer supported). All STP-A components and installation practices shall meet applicable building and safety codes.

STP-A Cable:

  • Color-coding:
    • Pair 1 Red/Green
    • Pair 2 Orange/Black
    • 0.63 mm (22 AWG) 150 ohm 2-pair enclosed by a shield.

       

  • Should be marked "150 ohm STP-A", in addition to any safety markings required by local or national codes.
  • Same mechanical and transmission requirements apply to backbone and horizontal cables. Additional requirements are provided for outdoor cables.

STP-A Connectors:

  • Standard outlet interface and pair assignments are the same as the ISO 8802-5 Token-Ring Connector (IEC 807-8) except that performance requirements are much more severe.
  • Should be marked "STP-A" in addition to any safety markings required by local or national codes.

STP-A Patch Cables:

  • Specifications call for 0.4 mm (26 AWG) stranded conductors.
  • Allows for an overall shield (as opposed to individually shielded pairs).
  • Less severe attenuation and NEXT loss than horizontal cable.

STP-A Installation Practices:

  • Shield shall be grounded at the Telecommunication Grounding Busbar.
  • Shield voltage to ground shall not exceed 1 Vrms at the work area.
  • Shield resistance to ground shall not exceed 3.5 W at the work area.
  • For runs between buildings with different ground potentials, optical fiber is recommended.